26
Toggle High Priority Display
Text (Maxi-
mum eight
characters)
Background Remarks
Primary
Pressure
Secondary
Pressure
Disabled A N Alarm Red Shows Alarm for second-
ary room if secondary room
is selected for display. If
the pressure to display is
selected as Primary, display
switches to the secondary
room to show the alarm.
Disabled A A Alarm Red Display toggles between pri-
mary and secondary room.
Disabled A A Alarm Red Display toggles between pri-
mary and secondary room.
Enabled N N Normal Green Toggle between primary and
secondary room.
Enabled N A Alarm Red Shows secondary alarm.
Display stops toggling.
Enabled N A Alarm Red Shows secondary alarm.
Display stops toggling.
Enabled A N Alarm Red Shows primary alarm. Dis-
play stops toggling.
Enabled A N Alarm Red Shows primary alarm. Dis-
play stops toggling.
Enabled A A Alarm Red Display toggles between pri-
mary and secondary room.
Enabled A A Alarm Red Display toggles between pri-
mary and secondary room.